Metered Quantities
List of Metered Quantities to be available through the API
This list is not final. It is a working list for review and discussion
Billing or Instrumentation | Source Description | Sources name |
---|---|---|
Billing | Active Energy = Wh, Total Delivered, Fundamental + harmonics | "kWh-Del" |
Billing | Active Energy = Wh, Total Received, Fundamental + harmonics | "kWh-Rec" |
Billing | Active Energy = Wh, Total Sum, Fundamental + harmonics | "kWh-Sum" |
Billing | Active Energy = Wh, Total Net, Fundamental + harmonics | "kWh-Net" |
Billing | Reactive Energy = VARh, Total Delivered, Fundamental + harmonics | "kVARh-Del" |
Billing | Reactive Energy = VARh, Total Received, Fundamental + harmonics | "kVARh-Rec" |
Billing | Reactive Energy = VARh, Total Sum, Fundamental + harmonics | "kVARh-Sum" |
Billing | Reactive Energy = VARh, Total Net, Fundamental + harmonics | "kVARh-Net" |
Billing | Reactive Energy = VARh, Q1+Q4, Fundamental + harmonics | "kVARh-(Q1+Q4)" |
Billing | Reactive Energy = VARh, Q2+Q3, Fundamental + harmonics | "kVARh-(Q2+Q3)" |
Billing | Reactive Energy = VARh, Q1, Fundamental + harmonics | "kVARh-Q1" |
Billing | Reactive Energy = VARh, Q2, Fundamental + harmonics | "kVARh-Q2" |
Billing | Reactive Energy = VARh, Q3, Fundamental + harmonics | "kVARh-Q3" |
Billing | Reactive Energy = VARh, Q4, Fundamental + harmonics | "kVARh-Q4" |
Billing | Arithmetic Apparent Energy = VAh, Total Delivered, Fundamental + harmonics | "kVAh-Del-arithmetic" |
Billing | Arithmetic Apparent Energy = VAh, Total Received, Fundamental + harmonics | "kVAh-Rec-arithmetic" |
Billing | Arithmetic Apparent Energy = VAh, Total Sum, Fundamental + harmonics | "kVAh-Sum-arithmetic" |
Billing | Active Energy = Wh, Total Delivered, Fundamental Only | "kWh-Del-fundamental" |
Billing | Active Energy = Wh, Total Received, Fundamental Only | "kWh-Rec-fundamental" |
Billing | Vectorial Apparent Energy = VAh, Total Sum: SQRT(Wh_sum^2+VARh_sum^2), Fundamental + harmonics | "kVAh-Sum" |
Billing | Vectorial Apparent Energy = VAh, Delivered: SQRT(Wh_del^2+[Q1+Q4]^2), Fundamental + harmonics | "kVAh-Del-(Q1+Q4)" |
Billing | Vectorial Apparent Energy = VAh, Received: SQRT(Wh_rec^2+[Q2+Q3]^2), Fundamental + harmonics | "kVAh-Rec-(Q2+Q3)" |
Billing | Vectorial Apparent Energy = VAh, Delivered: SQRT(Wh_del^2+[Q1]^2), Fundamental + harmonics | "kVAh-Del-Q1" |
Billing | Vectorial Apparent Energy = VAh, Received: SQRT(Wh_rec^2+[Q2]^2), Fundamental + harmonics | "kVAh-Rec-Q2" |
Billing | Vectorial Apparent Energy = VAh, Received: SQRT(Wh_rec^2+[Q3]^2), Fundamental + harmonics | "kVAh-Rec-Q3" |
Billing | Vectorial Apparent Energy = VAh, Delivered: SQRT(Wh_del^2+[Q4]^2), Fundamental + harmonics | "kVAh-Del-Q4" |
Billing | Power Factor (Arithmetic) = Wh, Delivered & VAh_arithmetic, Delivered: Fundamental + harmonics | "PF (kWh-Del and kVAh-Del-arithmetic)" |
Billing | Power Factor (Arithmetic) = Wh, Received & VAh_arithmetic, Received: Fundamental + harmonics | "PF (kWh-Rec and kVAh-Rec-arithmetic)" |
Billing | Power Factor (Arithmetic) = Wh, Sum & VAh_arithmetic, Sum: Fundamental + harmonics | "PF (kWh-Sum and kVAh-Sum-arithmetic)" |
Billing | Reactive Energy = VARh, Total Delivered, Fundamental Only | "kVARh-Del-fundamental" |
Billing | Reactive Energy = VARh, Total Received, Fundamental Only | "kVARh-Rec-fundamental" |
Billing | Power Factor (Vectorial) = Wh, Delivered & VARh, Q1+4: Fundamental + harmonics | "PF (kWh-Del and kVARh-Q1+Q4)" |
Billing | Power Factor (Vectorial) = Wh, Received & VARh, Q2+3: Fundamental + harmonics | "PF (kWh-Rec and kVARh-Q2+Q3)" |
Instrumentation | Frequency | "Line frequency" |
Instrumentation | Current rms, phase A, Fundamental + harmonics | "Phase A Current" |
Instrumentation | Current rms, phase B, Fundamental + harmonics | "Phase B Current" |
Instrumentation | Current rms, phase C, Fundamental + harmonics | "Phase C Current" |
Instrumentation | Voltage rms, phase A, Fundamental + harmonics | "Phase A Voltage" |
Instrumentation | Voltage rms, phase B, Fundamental + harmonics | "Phase B Voltage" |
Instrumentation | Voltage rms, phase C, Fundamental + harmonics | "Phase C Voltage" |
Instrumentation | Active Power = Watts, Phase A, Fundamental + harmonics | "Phase A kW" |
Instrumentation | Active Power = Watts, Phase B, Fundamental + harmonics | "Phase B kW" |
Instrumentation | Active Power = Watts, Phase C, Fundamental + harmonics | "Phase C kW" |
Instrumentation | Active Power = Watts, System, Fundamental + harmonics | "System kW" |
Instrumentation | Reactive Power = VARs, Phase A, Fundamental + harmonics | "Phase A kVAR" |
Instrumentation | Reactive Power = VARs, Phase B, Fundamental + harmonics | "Phase B kVAR" |
Instrumentation | Reactive Power = VARs, Phase C, Fundamental + harmonics | "Phase C kVAR" |
Instrumentation | Reactive Power = VARs, System, Fundamental + harmonics | "System kVAR" |
Instrumentation | Apparent Power = VAs, Phase A, Fundamental + harmonics | "Phase A kVA" |
Instrumentation | Apparent Power = VAs, Phase B, Fundamental + harmonics | "Phase B kVA" |
Instrumentation | Apparent Power = VAs, Phase C, Fundamental + harmonics | "Phase C kVA" |
Instrumentation | Arithmetic Apparent Power = VAs, System, Fundamental + harmonics | "System kVA - arithmetic " |
Instrumentation | Vectorial Apparent Power = VAs, System, Fundamental + harmonics | "System kVA - vectorial" |
Instrumentation | Rounded Phase A Voltage to Phase A Voltage Phase Angle | "Phase A Voltage Angle" |
Instrumentation | Rounded Phase B Voltage to Phase A Voltage Phase Angle | "Phase B Voltage Angle" |
Instrumentation | Rounded Phase C Voltage to Phase A Voltage Phase Angle | "Phase C Voltage Angle" |
Instrumentation | Angle of Current to Va, Phase A = Current to Phase A Voltage, Fundamental + harmonics | "Phase A Current Angle" |
Instrumentation | Angle of Current to Va, Phase B = Current to Phase A Voltage, Fundamental + harmonics | "Phase B Current Angle" |
Instrumentation | Angle of Current to Va, Phase C = Current to Phase A Voltage, Fundamental + harmonics | "Phase C Current Angle" |
Instrumentation | Power Factor, Phase A = W & VA, Fundamental + harmonics | "Phase A PF" |
Instrumentation | Power Factor, Phase B = W & VA, Fundamental + harmonics | "Phase B PF" |
Instrumentation | Power Factor, Phase C = W & VA, Fundamental + harmonics | "Phase C PF" |
Instrumentation | Power Factor, Arithmetic, System = W & VA(arithmetic), System, Fundamental + harmonics | "System PF - arithmetic" |
Instrumentation | Power Factor, Vectorial, System = W & VA(vectorial), System, Fundamental + harmonics | "System PF - vectorial" |
Instrumentation | Current rms, phase A, Fundamental Only | "Phase A Current - fundamental" |
Instrumentation | Current rms, phase B, Fundamental Only | "Phase B Current - fundamental" |
Instrumentation | Current rms, phase C, Fundamental Only | "Phase C Current - fundamental" |
Instrumentation | Voltage rms, phase A, Fundamental Only | "Phase A Voltage - fundamental" |
Instrumentation | Voltage rms, phase B, Fundamental Only | "Phase B Voltage - fundamental" |
Instrumentation | Voltage rms, phase C, Fundamental Only | "Phase C Voltage - fundamental" |
Instrumentation | Current rms, phase A, 2nd_Harmonic | "Phase A Current - 2nd Harmonic" = 75, |
Instrumentation | Current rms, phase B, 2nd_Harmonic | "Phase B Current - 2nd Harmonic" = 76, |
Instrumentation | Current rms, phase C, 2nd_Harmonic | "Phase C Current - 2nd Harmonic" = 77, |
Instrumentation | Voltage rms, phase A, 2nd_Harmonic | "Phase A Voltage - 2nd Harmonic" = 78, |
Instrumentation | Voltage rms, phase B, 2nd_Harmonic | "Phase B Voltage - 2nd Harmonic" = 79, |
Instrumentation | Voltage rms, phase C, 2nd_Harmonic | "Phase C Voltage - 2nd Harmonic" = 80, |
Instrumentation | Total Harmonic Distortion Percentage, Current, Phase A | "Phase A Current % THD" = 81, |
Instrumentation | Total Harmonic Distortion Percentage, Current, Phase B | "Phase B Current % THD" = 82, |
Instrumentation | Total Harmonic Distortion Percentage, Current, Phase C | "Phase C Current % THD" = 83, |
Instrumentation | Total Harmonic Distortion Percentage, Voltage, Phase A | "Phase A Voltage % THD" = 84, |
Instrumentation | Total Harmonic Distortion Percentage, Voltage, Phase B | "Phase B Voltage % THD" = 85, |
Instrumentation | Total Harmonic Distortion Percentage, Voltage, Phase C | "Phase C Voltage % THD" = 86 |
Instrumentation | Reactive Power = VARs(Arithmetic), System, Fundamental + harmonics | "System kVAR - arithmetic" |
Billing | Active Energy = Wh, Total Sum, Fundamental Only | "kWh-Sum-fundamental" |
Billing | Active Energy = Wh, Total Net, Fundamental Only | "kWh-Net-fundamental" |
Billing | Reactive Energy = VARh, Q1, Fundamental Only | "kVARh-Q1-fundamental" |
Billing | Reactive Energy = VARh, Q2, Fundamental Only | "kVARh-Q2-fundamental" |
Billing | Reactive Energy = VARh, Q3, Fundamental Only | "kVARh-Q3-fundamental" |
Billing | Reactive Energy = VARh, Q4, Fundamental Only | "kVARh-Q4-fundamental" |
Billing | Reactive Energy = VARh, Q1+Q4, Fundamental Only | "kVARh-(Q1+Q4)-fundamental" |
Billing | Reactive Energy = VARh, Q2+Q3, Fundamental Only | "kVARh-(Q2+Q3)-fundamental" |
Billing | Arithmetic Apparent Energy = VAh, Total Delivered, Fundamental Only | "kVAh-Del-fundamental" |
Billing | Arithmetic Apparent Energy = VAh, Total Received, Fundamental Only | "kVAh-Rec-fundamental" |
Instrumentation | Current rms, Neutral imputed, Fundamental + harmonics | "Neutral Imputed Current" |
Instrumentation | Load Side Voltage |
|
Instrumentation | Power Factor Angle, Phase A = Current to Voltage (same phase), Fundamental + harmonics | "Phase A PF Angle" |
Instrumentation | Power Factor Angle, Phase B = Current to Voltage (same phase), Fundamental + harmonics | "Phase B PF Angle" |
Instrumentation | Power Factor Angle, Phase C = Current to Voltage (same phase), Fundamental + harmonics | "Phase C PF Angle" |
Instrumentation | Temperature (degF) | "Temperature (F)" |
Instrumentation | Temperature (degC) | "Temperature (C)" |
Instrumentation | 2nd Harmonic Voltage Percentage, Phase A | "Phase A Voltage % 2nd Harmonic" |
Instrumentation | 2nd Harmonic Voltage Percentage, Phase B | "Phase B Voltage % 2nd Harmonic" |
Instrumentation | 2nd Harmonic Voltage Percentage, Phase C | "Phase C Voltage % 2nd Harmonic" |
Instrumentation | Total Demand Distortion Percentage, Current, Phase A | "Phase A Current % TDD" |
Instrumentation | Total Demand Distortion Percentage, Current, Phase B | "Phase B Current % TDD" |
Instrumentation | Total Demand Distortion Percentage, Current, Phase C | "Phase C Current % TDD" |
Instrumentation | Power Factor Angle, Arithmetic, System, Fundamental + harmonics | "System PF Angle - arithmetic" |
Instrumentation | Power Factor Angle, Vectorial, System, Fundamental + harmonics | "System PF Angle - vectorial" |
Instrumentation | Distortion Current rms, Phase A | "Phase A Harmonic Current" |
Instrumentation | Distortion Current rms, Phase B | "Phase B Harmonic Current" |
Instrumentation | Distortion Current rms, Phase C | "Phase C Harmonic Current" |
Instrumentation | Demand - Active Power = Watts, Phase A, Fundamental + harmonics |
|
Instrumentation | Demand - Active Power = Watts, Phase B, Fundamental + harmonics |
|
Instrumentation | Demand - Active Power = Watts, Phase C, Fundamental + harmonics |
|
Instrumentation | Demand - Active Power = Watts, System, Fundamental + harmonics |
|
Instrumentation | Demand - Reactive Power = VARs, Phase A, Fundamental + harmonics |
|
Instrumentation | Demand - Reactive Power = VARs, Phase B, Fundamental + harmonics |
|
Instrumentation | Demand - Reactive Power = VARs, Phase C, Fundamental + harmonics |
|
Instrumentation | Demand - Reactive Power = VARs, System, Fundamental + harmonics |
|
Instrumentation | Demand - Apparent Power = VAs, Phase A, Fundamental + harmonics |
|
Instrumentation | Demand - Apparent Power = VAs, Phase B, Fundamental + harmonics |
|
Instrumentation | Demand - Apparent Power = VAs, Phase C, Fundamental + harmonics |
|
Instrumentation | Demand - Arithmetic Apparent Power = VAs, System, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Active Power = Watts, Phase A, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Active Power = Watts, Phase B, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Active Power = Watts, Phase C, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Active Power = Watts, System, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Reactive Power = VARs, Phase A, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Reactive Power = VARs, Phase B, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Reactive Power = VARs, Phase C, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Reactive Power = VARs, System, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Apparent Power = VAs, Phase A, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Apparent Power = VAs, Phase B, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Apparent Power = VAs, Phase C, Fundamental + harmonics |
|
Instrumentation | Maximum Demand - Arithmetic Apparent Power = VAs, System, Fundamental + harmonics |
|
Name plate | Meter serial number |
|
Name plate | Meter model info |
|
Name plate | Meter type info |
|
Name plate | Basic current |
|
Name plate | Maximum current |
|
Name plate | Minimum voltage |
|