IEC 61850 requires PTP (precision time protocol) synchronization synchronization between the different physical and virtual machines.
In the context of IEC 61850, it is used for communication between the machines (with SV, GOOSE or MMS protocol). In SEAPATH, this synchronization synchronization is also used between the different machines to form the cluster.
PTP is a Transmitter/Receiver architecture. It uses a Grand master clock
, a physical device that will be the reference time. All other machines and devices synchronize themselves with it.
Connectivity
The grand master clock and the physical machines are connected with an Ethernet cable. In a very simple scenario, the cable can be plugged directly from the clock to the machine.
...
Below is a schema of the connectivity with a switch.
...
Hypervisor synchronization
The hosts synchronize the time with both NTP and PTP. This is done by the timemaster
service during the network configuration section.
Three tools are used:
chrony
synchronize the system clock with NTP. The NTP server can be configured to be on the local network or on the internet.ptp4l
synchronize the hardware clock (PHC) with PTP.phc2sys
synchronize hardware and system clocks.
...
To see the status of the clocks and the delay with the references, use the command
Code Block | ||
---|---|---|
| ||
chronyc sources |
Logs of timemaster service are also useful to spot any errors:
Code Block | ||
---|---|---|
| ||
systemctl status timemaster |
Virtual machine synchronization
The VM’s clock can be synchronized in two ways.
PCI-passthrough
The network interface that receives PTP frames from the grand master clock can be configured in PCI-passthrough in order to be fully available inside the virtual machine. When doing that, a PTP clock will automatically be created inside the VM, it can be managed by timemaster. Refer to the hypervisor section.
Be aware that in this case, two interfaces must receive PTP frames: one to synchronize the host and one to synchronize the virtual machine.
PTP_KVM
Linux can make the PTP clock of the hypervisor available inside the virtual machine. This is done by the kernel module ptp_kvm
. TheThe clock is derived from the hypervisor’s and is thus already synchronized.
To achieve this, inside the VM, you must
Load the kernel module
ptp_kvm
, either automatically at boot or manually.
This will create a ptp device in/dev/.
To determine which device is the one created byptp_kvm
, simply check that the file/sys/class/ptp/ptp*/clock_name
does indeed say "KVM virtual PTP".
In this example, ourptp_kvm
device is ptp0.Synchronize the system clock with the PTP clock.
This can be done with the tool p
hc2sy
s
from phc2sys
from the linuxptp package :
Code Block |
---|
phc2sys -s /dev/ptp0 -c CLOCK_REALTIME -O 0 -m -q |
...
Code Block |
---|
refclock PHC /dev/ptp0 poll 3 dpoll -2 offset 0 |
...
Grand master simulation
Warning: This section is for test only. It is not intended to be used in a real environment.
To avoid the use of a physical grand master clock, a standard machine like a laptop can be used to simulate the PTP reference time. This is called « software PTP ».
To achieve that :
Install
linuxptp
package on the laptop.Configure the PTP settings, in the file /etc/linuxptp/ptp4l.conf
Starts the
ptp4l
service.
The configuration of PTP is fixed by IEC-61850 (see here on Wikipedia). Here is a proposed configuration of the file /etc/linuxptp/ptp4l.conf that fits the standard requirements.
Code Block |
---|
[Global] slaveOnly 0 gmCapable 1 domainNumber 0 # Announce interval: 1s logAnnounceInterval 0 # Sync interval: 1 s logSyncInterval 0 # Pdelay interval: 1 s logMinPdelayReqInterval 0 # Announce receipt time-out: 3 s (fixed) announceReceiptTimeout 3 priority1 128 priority2 128 # Default clock class : any specialised clock will be better (ie a GPS Grand Master Clock) #clockClass 192 network_transport L2 delay_mechanism P2P clockClass 248 clockAccuracy 0xFE offsetScaledLogVariance 0xFFFF |
Info |
---|
The PTP clock created by ptp4l will not be synchronized with the current time. So even if your cluster machines are synchronized with each other, the date will be random. phc_ctl <ptp_interface> set |
Troubleshooting
rogue peer delay response