Code Block | ||
---|---|---|
| ||
{
"protocol_stack":{
"name":"hnzserver",
"version":"1.0",
"transport_layer":{
"port_path_A":6001
"port_path_B":6002
},
"application_layer":{
"remote_station_addr":12,
"inacc_timeout":180,
"max_sarm":30,
"repeat_path_A":3,
"repeat_path_B":3,
"repeat_timeout":3000,
"anticipation_ratio":3,
"test_msg_send":"1304",
"test_msg_receive":"1304",
"gi_schedule":"99:99",
"gi_repeat_count":3,
"gi_time":255,
"c_ack_time":10,
"cmd_recv_timeout":100000
},
}
} |
HNZ datapoint representation
...
Attribute | Description | Expected values | Mandatory |
---|---|---|---|
do_type | message type | TS, TM, TC, TVC | YES |
do_station | station address | YES | |
do_addressaddr | message address | YES | |
do_value | value | TM (do_an = TMA): [-127..127] TM (do_an = TM8): [0..255] TM (do_an = TM16): [-32768..32767] TS: [0..1] TC: [1..2] (01b = on, 10b = off) TVC: [-255..255] | YES except in quality update readings |
do_valid | validity | valid = 0 or invalid = 1 | YES |
do_an | TM type (analogic / numeric) | "TMA", "TM8", "TM16" | TM only |
do_cg | TS source | CG = 1 or CE = 0 | TS only |
do_outdated | Outdated message (after connection loss) | up to date =0, outdated = 1 | TM and TS only |
do_ts | timestamp | epoch timestamp in milliseconds | TS CE only |
do_ts_iv | timestamp invalid | valid = 0 or invalid = 1 (from bit HNV) | TS CE only |
do_ts_c | loss of chronology | lost = 1 else = 0 (from bit CV) | TS CE only |
do_ts_s | ts not synchronized | synchronized = 0 else = 1 (from bit S) | TS CE only |
...
NB: if an attribute is not required, then it is not put in the output data object, which means that the output object structure always fits the protocol model object type.
HNZ command representation
Commands are not implemented