IEC 61850 Protocol stack configuration
...
Attributes | Definition | Example | Required |
---|---|---|---|
polling_interval | defines the polling interval in ms (0 = no polling) | 100 | Yes |
datasets | Array of datasets | No | |
datasets.dataset_ref | Dataset reference | Yes | |
datasets.entries | Array of dataset entries, each entry is build using this pattern: iedName+ldInst/prefix+lnClass+lnInst+doName NB: prefix is optional |
This entry in the CID file code: <FCDA ldInst="GenericIO" lnClass="GGIO" fc="MX" lnInst="1" doName="AnIn1" daName="mag.f" />should be translated to:
| Yes |
datasets.dynamic | If dataset is set to dynamic = true then the client would try to create the dataset on the server, default is false (Static) | No | |
report_subscriptions | Array of report subscriptions | No | |
report_subscriptions.rcb_ref | Report Control Block Reference | Yes | |
report_subscriptions.dataset_ref | RCB dataset reference | No | |
report_subscription.trgops | RCB trigger options | ["data_changed","quality_changed", "integrity", ...] | No |
report_subscription.buftm | RCB buffer time in ms, time to wait before sending value after event occured | No | |
report_subscription.intgpd | RCB integrity period in ms, report is periodically send for the period defined (this requires the trgops to be set to "integrity") | No | |
report_subscription.gi | Force GI (General Interrogation) when the RCB is enabled | No |
...